型号 : | PJP-8、PJP-16 | 加工定制 : | 是 |
品牌 : | 安航 |
消防水/泡沫软管站PJP-8、PJP-16,比例混合器流量范围为:48L/s、816L/s,容积为300L(可根据实际工程确定),工作压力范围:0.6-1.2MPa,混合比为3,卷盘长度20m,泡沫 射程18m。
消防水软管站SJP-8、SJP-16,比例混合器流量范围为:48L/s、816L/s,工作压力范围:0.6-1.2MPa,卷盘长度20m,泡沫 射程1828m。
I. Introduction
Fire water / foam hose reel station PJP-8, PJP-16, the flow range of proportioning mixer is 4 8L / s, 8 16L / s, the volume is 300L (according to the actual engineering), the range of working pressure is 0.6 -1.2MPa, the mixing ratio is 3, the length of reel is 20m, foam gun range 18m.
Fire hose reel stations SJP-8, SJP-16, the flow range of proportioning mixer is 4 8L / s, 8 16L / s, the range of working pressure is 0.6 -1.2MPa, the length of reel is 20m, the range of foam gun is greater than or equal to 18 28m.
1、构造Structure
消防水/泡沫软管站构造如上图所示
The structure of fire water/foam hose reel station as pictured above
消防水软管站构造如上图所示
The structure of fire water hose reel station as pictured above
2、工作原理
1)消防水/泡沫软管站
消防水从泡沫比例混合器入口通过,泡沫液经比例混合器混合后,通过软管至泡沫 打出泡沫混合液,实施灭火。
2)消防水软管站
消防水经过软管站软管至直流喷雾水枪,实施灭火。
2. Working principle
1) Fire water / foam hose reel station
Fire water gets in through the inlet of the foam proportioner, and spray out the foam solution through the hosepipe to foam gun after foam liquid mixed by the hybrid device, and then put out the fire.
2) Fire water hose reel station.
Fire water is transmitted into DC spray nozzle through the hose of the hose station to put out the fire.
二、设备的基本参数The basic parameters of the device
2.1、性能参数:The performance parameters
表Table 1
名称 Name | 型号 Type | 工作压力范围 Working pressure | 额定工作压力rated working pressure | 储罐容量 Storage tank volume | 混合比 Mixing ratio | 流量范围 The range of flow | 射程 Range | 进出口压差 Differential pressure between inlet and outlet |
消防水/泡沫软管站 Fire water / foam hose reel station | PJP-8 | 0.6-1.2MPa | 0.7 MPa | 100700L(可根据实际工程确定) According to the actual engineering | 3 或6 | 8L/s±8 | 18m | 0.2MPa |
PJP-16 | 16L/s±8 |
表Table 2
名称Name | 型号Type | 工作压力范围 Working pressure | 额定工作压力Rated working pressure | 流量范围 The range of flow | 射程 Range |
消防水软管站 Fire water hose reel station | SJP-8 | 0.6-1.2MPa | 0.7 MPa | 8L/s±8 | 1828m |
SJP-16 | 16L/s±8 |
2.2软管站安装尺寸及质量(不含泡沫液)
The installation dimension and quality of hose reel station (Excluding foam liquid)
表Table 3
名称Name | 型号 Type | 消防水进口通径(mm) Inlet diameter of fire water(mm) | 外形尺寸(mm) Outside dimension | 重量(kg) Weight |
消防水/泡沫软管站 Fire water / foam hose reel station | PJP-8 | DN50 | 680×560×1245 | 180 |
PJP-16 | ||||
消防水软管站 Fire water hose reel station | SJP-8 | 130 | ||
SJP-16 |